PT100 thermal resistance sensor input, PID temperature control accuracy, small fluctuations, menu type operation page, easy to understand, easy to operate. It has 120 groups of programs, with a maximum of 100 segments per group, and a running time of 99 hours and 99 minutes per segment, which can meet almost all complex experimental processes. Provide fault short message alarm signal source: automatically stop operation when the temperature and pressure exceed the limit, and prompt the operator through the fault short message alarm system to ensure the safe operation of the experiment without accidents. Convenient data processing, can be connected to a printer or computer, and can record changes in temperature and humidity data. With three-level permissions and an electronic signature function, it meets the United States GMP drug regulatory norms.
1. 5-inch color touch screen; TFT resolution: 480 × 272;
2. Control mode: fixed value/program;
3. Sensor type: PT100 sensor input (optional electronic sensor);
4. Temperature measurement range: - 90.0 ºC~200.0 ºC (- 90 ºC~300 ºC can be specified), with an error of ± 0.2 ºC;
6. Contact input: Input type: 1. RUN/STOP, 2. 8-way DI fault input; Input form: maximum contact capacity: 12V DC/10mA;
7. Control output type: voltage pulse (SSR); Control output: 1 channel (temperature);
8. Contact output: contact maximum 8 points, contact capacity: maximum 30V DC/5A, 250V AC/5A;
9. Contact output type:
(1) T1-T8: 8:00 (2) Internal contact IS: 8:00 (3) Time signal TS: 4:00 (4) Temperature RUN: 1:00
(5) Temperature UP: 1 point (6) Temperature DOWN: 1 point
(7) Temperature Soak: 1 point (8) Drain: 1 point (9) Fault: 1 point (10) Program end: 1 point
(11) 1st Ref: 1 point (12) 2nd Ref: 1 point (13) Alarm: 4 points (optional alarm type);
10. Communication interface: RS232/RS485, with a maximum communication distance of 1.2km. It can be connected to a printer to print temperature curve monitoring data;
11. Program editing: 120 groups of programs can be compiled, with a maximum of 100 segments per group of programs;
12. Interface language type: Chinese/English;
13. PID number/program connection: 9 temperature groups/each program can be connected;
14. Power supply: touch screen: DC 24V; Lower computer: 85-265V AC, 50/60Hz;
15. Insulation level: 2000V AC/1 minute.
Outline and installation dimensions:
Overall dimension: 173 × one hundred and three × 39 (mm) (length × wide × Deep)
Installation hole size: 162 × 92 (mm) (length × Width)